TACHx receives signals from a fan, And this value can be read from related register.
The READ_FAN_SPEED_1 command returns the fan speed in RPM", so if the speed is out of the desired range you know…
Configuring the FAULT pin as an input pin via the MFR_FAULT_RESPONSE(register 0xD9) Bit0 = '1' will force the fan output to 100% duty cycle when the pin is externally asserted. Bit 0 of the MFR_FAULT_RESPONSE…
Configuring the FAULT pin as an input pin via the MFR_FAULT_RESPONSE(register 0xD9) Bit0 = '1' will force the fan output to 100% duty cycle when the pin is externally asserted. Bit 0 of the MFR_FAULT_RESPONSE…
Page 0-22 (decimal) is used to select individual fan, temperature sensor, or remote voltage connected to the ADC. For control associated with each page, refer to Table 9 in the datasheet (Rev 3 8/12).…